Ledger / #160
dispatch crew on transformer 2538
T1 done- incident
- transformer overload inc_b680682e0659
- when
- Tue 20:00
- call
- POST /wfm/work-orders feeder=791 transformer=2538 purpose=thermal_inspection
- decided by
- rules
- definition
- transformer_overload v1
- why
- Loading 131% of the rating for 2 hours: send a crew for a thermal check.
- controller
- Allowed: dispatch_crew is tier 1 (do it and tell); within budget (0 of 12 actions on feeder 791 this hour).
- outcome
- Crew C-11 sent to FNF2-15/T02 for a thermal inspection, 9.6 km away.
- at stake
- 41 customers on a transformer at 131.2% of its rating
Evidence
| customer_minutes | None |
|---|---|
| customers_at_stake | 41 |
| feed | network |
| feeder_id | 791 |
| hours_over | 2 |
| last_hour | 2026-11-10 19:00:00 |
| peak_kva | 413.4 |
| peak_pct | 131.2 |
| priority_at_stake | None |
| rating_kva | 315 |
| stake_note | 41 customers on a transformer at 131.2% of its rating |
| started_at | 2026-11-10T18:00:00 |
| transformer | FNF2-15/T02 |
| transformer_id | 2538 |
Arguments
| feeder_id | 791 |
|---|---|
| purpose | thermal_inspection |
| transformer_id | 2538 |