Ledger / #518
request load reduction on transformer 1783
T2 approved- incident
- transformer overload inc_db1d1c49435c
- when
- Sat 19:07
- call
- POST /scada/load-transfers transformer=1783 target=299 kVA
- decided by
- rules · Tamsin K. (control engineer on duty, scripted)
- definition
- transformer_overload v1
- why
- Loading reached 151% of the rating for 2 hours: move load off it; a person approves.
- controller
- Needs a person: request_load_reduction is tier 2 (ask first) in the policy. Move load off an overloaded transformer (switch customers to a neighbour, or call the flexibility contracts).
- outcome
- move the two street cables to the neighbouring transformer tonight [scripted on-call responses (synthetic)]
- at stake
- 78 customers on a transformer at 151.4% of its rating
Evidence
| customer_minutes | None |
|---|---|
| customers_at_stake | 78 |
| feed | network |
| feeder_id | 552 |
| hours_over | 2 |
| last_hour | 2026-11-14 18:00:00 |
| peak_kva | 476.8 |
| peak_pct | 151.4 |
| priority_at_stake | None |
| rating_kva | 315 |
| stake_note | 78 customers on a transformer at 151.4% of its rating |
| started_at | 2026-11-14T17:00:00 |
| transformer | THR2-07/T01 |
| transformer_id | 1783 |
Arguments
| target_kva | 299 |
|---|---|
| transformer_id | 1783 |