Ledger / #624
dispatch crew on transformer 1193
T1 done- incident
- transformer overload inc_a9691b8e0213
- when
- Sat 20:00
- call
- POST /wfm/work-orders feeder=368 transformer=1193 purpose=thermal_inspection
- decided by
- rules
- definition
- transformer_overload v1
- why
- Loading 147% of the rating for 2 hours: send a crew for a thermal check.
- controller
- Allowed: dispatch_crew is tier 1 (do it and tell); within budget (0 of 12 actions on feeder 368 this hour).
- outcome
- Crew C-03 sent to OKD3-13/T01 for a thermal inspection, 18.9 km away.
- at stake
- 88 customers on a transformer at 147.0% of its rating
Evidence
| customer_minutes | None |
|---|---|
| customers_at_stake | 88 |
| feed | network |
| feeder_id | 368 |
| hours_over | 2 |
| last_hour | 2026-11-14 19:00:00 |
| peak_kva | 463.1 |
| peak_pct | 147.0 |
| priority_at_stake | None |
| rating_kva | 315 |
| stake_note | 88 customers on a transformer at 147.0% of its rating |
| started_at | 2026-11-14T18:00:00 |
| transformer | OKD3-13/T01 |
| transformer_id | 1193 |
Arguments
| feeder_id | 368 |
|---|---|
| purpose | thermal_inspection |
| transformer_id | 1193 |