dispatch crew on transformer 665
T3 declined- incident
- transformer overload inc_92ba52968f19
- when
- Sat 22:00
- call
- POST /wfm/work-orders feeder=208 transformer=665 purpose=thermal_inspection
- decided by
- rules
- definition
- transformer_overload v1
- why
- Loading 143% of the rating for 2 hours: send a crew for a thermal check.
- controller
- Declined, because dispatch_crew ran on the same target 60 min ago; the cooldown is 120 min.
- outcome
- Declined, because dispatch_crew ran on the same target 60 min ago; the cooldown is 120 min.
- at stake
- 105 customers on a transformer at 143.0% of its rating
Evidence
| customer_minutes | None |
|---|---|
| customers_at_stake | 105 |
| feed | network |
| feeder_id | 208 |
| hours_over | 2 |
| last_hour | 2026-11-14 20:00:00 |
| peak_kva | 450.4 |
| peak_pct | 143.0 |
| priority_at_stake | None |
| rating_kva | 315 |
| stake_note | 105 customers on a transformer at 143.0% of its rating |
| started_at | 2026-11-14T19:00:00 |
| transformer | CRB14-14/T02 |
| transformer_id | 665 |
Arguments
| feeder_id | 208 |
|---|---|
| purpose | thermal_inspection |
| transformer_id | 665 |