Ledger / #922
dispatch crew on transformer 561
T3 declined- incident
- transformer overload inc_35b349972c73
- when
- Sat 23:00
- call
- POST /wfm/work-orders feeder=172 transformer=561 purpose=thermal_inspection
- decided by
- rules
- definition
- transformer_overload v1
- why
- Loading 134% of the rating for 3 hours: send a crew for a thermal check.
- controller
- Declined, because dispatch_crew ran on the same target 60 min ago; the cooldown is 120 min.
- outcome
- Declined, because dispatch_crew ran on the same target 60 min ago; the cooldown is 120 min.
- at stake
- 102 customers on a transformer at 133.9% of its rating
- repeats
- 1 later sightings folded into this row
Evidence
| customer_minutes | None |
|---|---|
| customers_at_stake | 102 |
| feed | network |
| feeder_id | 172 |
| hours_over | 3 |
| last_hour | 2026-11-14 22:00:00 |
| peak_kva | 421.9 |
| peak_pct | 133.9 |
| priority_at_stake | None |
| rating_kva | 315 |
| stake_note | 102 customers on a transformer at 133.9% of its rating |
| started_at | 2026-11-14T20:00:00 |
| transformer | CRB12-07/T04 |
| transformer_id | 561 |
Arguments
| feeder_id | 172 |
|---|---|
| purpose | thermal_inspection |
| transformer_id | 561 |